Generator Sizing

Generator AMP Chart — Full-Load Amps by Size & Voltage

Use this generator amp chart to match a diesel generator's full-load amps (FLA) to your electrical load. Find your generator size, then read across to your voltage and phase. Figures are approximate at a 0.8 power factor — use them for planning and call us to confirm sizing.

Generator Size120V 1Ø120V 3Ø240V 1Ø208V 3Ø480V 3Ø
20 kW25104608330
30 kW361569012545
45 kW5423413518868
56 kW6729216923484
60 kW7231318125090
100 kW120521301417150
125 kW150651376521188
150 kW180781451625225
175 kW210911526729263
200 kW2401042602833301
230 kW2761198692958346
250 kW30013027521042376
300 kW36015629031250451
320 kW38516679631333481

1Ø = single phase · 3Ø = three phase · FLA shown at ~0.8 power factor. Actual amperage varies with load and power factor.

Generator Sizing CalculatorCompare Generator SizesCall (415) 644-5792

How to use the amp chart

Add up the running amps of everything you need to power, then account for the higher startup (surge) amps of the largest motor. Match that total to a generator size at your service voltage. When a load is close to a generator's rated amps, size up to the next unit to keep headroom for surges.

Frequently asked questions

How do I read the generator amp chart?
Find your generator's kW size in the left column, then read across to the voltage you're running. The number is the approximate full-load amps (FLA) that size can deliver at that voltage.
What is FLA (full-load amps)?
Full-load amps is the current a generator delivers at its rated output. Match it to your equipment's amperage draw and panel rating to size correctly.
Single-phase vs three-phase amps?
At the same kW, three-phase delivers lower amps per leg than single-phase, which is why large loads use three-phase. The chart lists both so you can match your service.
Are these amp figures exact?
They're planning estimates based on a 0.8 power factor. Actual amperage varies with power factor, voltage and load. Call us to confirm sizing for your job.